Level control Min. or Max. of highly resistive conductive liquids: Demineralized water (5 to 20 MOhm), Glycerine (1 MOhm), etc. The RXM detects the difference of resistance between the detection electrode and the reference electrode when the liquid comes into contact. The reference can be the wall of the metal container or a second electrode. To carry out this detection, a DC voltage of 12V is applied between the electrode and the reference. The value of the resistor to detect varies according the liquid and distances to cover between the electrode and the reference. 533100.
Limit detection adjustment: The detection limit of the RXM is defined as the maximum value of the resulting resistance of the product for which the detection can occur.
- The detection limit is adjustable between 4.7 to 100 MOhm.
- Take care to use the specific coaxial cable to connect the electrodes to the relay RXM.
- The detection limit potentiometer is accessible after taking off the transparent plastic lid.
Resistive probes:
Choose the right probe according to operating conditions and the chemical compatibilities (liquid, pressure, temperature, etc.).