Three-phase thyristor power controller in three-phase economy circuit (two of three phase). The JUMO TYA 202 represents the systematic further development of the JUMO power controller technology. It switches resistive inductive loads using a three-phase economy circuit in star-delta three-phase operation. It is used where larger resistive and inductive loads have to be switched.
- Subordinate: control loop U, U2 (standard), I, I2, P (optional)
- Load type: Resistive load, resistive inductive load, cold/warm ratio 1:16, transformer load, infrared emitter (short, medium, long-wave)
- Load voltage: 24 V, 42 V, 115 V, 230 V, 400 V, 460 V, 500 V
- Load currents: 20 A, 32 A, 50 A, 100 A, 150 A, 200 A, 250 A
- Approval: cULus
- Special features: Economy circuit, mains load optimization, dual energy management, "Teach-In" function (partial load failure detection), "r-control" (resistance limitation), intelligent diagnosis system, integrated semiconductor fuse, device configuration without auxiliary voltage, vibrant display, "True RMS" (root mean square)
- Control voltage: Control voltage = load voltage
- Operating modes: Burst-firing operation, SSR logical operation, fast logical operation, alpha start, soft start
- Ambient temperature: -20 to +70°C
- System interfaces: Modbus, PROFIBUS DP, system bus JUMO mTRON T, PROFINET, EtherCAT
- Configuration: Setup/USB-powered; plain text display on the device
Stock models with short delivery times:
709062/8-01-020-100-400-00/252 |
709062/8-01-032-100-400-00/252 |
709062/8-01-050-100-400-00/252 |
709062/8-01-100-100-400-00/252 |
709062/8-01-100-010-400-00/252 |
709062/8-01-150-010-400-00/252 |
709062/8-01-200-100-400-00/252 |
709062/8-01-200-010-400-00/252 |
709062/8-01-250-100-400-00/252 |
|
|